Tiêu chuẩn cấp gió tươi và thông gió điều hòa .Singapor standard SS CP13 : 1999
Code of practive for mechanical ventilation and air -conditionning in buidings.
Code of practive for mechanical ventilation and air -conditionning in buidings.
Table 1 - Outdoor air supply requirement for comfort air-conditioning | ||
Type of buiding/ Occupancy | Minimum outdoor air supply L/s per floor area | m³/h per m² floor area |
Restaurants | 2.80 | 10.00 |
Dance halls | 5.30 | 19.00 |
Ofiices | 0.65 | 2.30 |
Shop, supermarkets and department stores | 1.00 | 3.60 |
Lobbies, concourses and corridors | 0.25 | 0.90 |
Classrooms | 2.60 | 9.20 |
Theatres and cinemas | 2.00 | 7.30 |
Factories and workshops | ||
Light | 1.20 | 4.30 |
Medium | 0.70 | 2.60 |
High | 0.35 | 1.30 |
Hotel guest rooms | 15 L/s per room | 54 m³/h per room |
Table 2- Outdoor air supply for mechanical ventilation in non-conditioned buidings | |
Type of buiding Occupancy | minimum outdoor air supply Air-change/h |
Ofiice | 6 |
Restaurant ,canteens | 10 |
Shop, supermarkets and department stores | 6 |
Workshops ,factories | 6 |
Classrooms | 8 |
Theatres and cinemas | 8 |
Lobbies ,concourse , conffidors , staircases and exit | 4 |
Tolets , bathrooms | 10 |
Kitchens (commercial ,institutional and industrial | 20 |
Car Parks | 6 |
Fire commmand center | 6 |
Civil Defence shelters | 16 |
Wasterwater facilities/pumping installation | 8 |
Xêm thêm chi tiết bên dưới (Thời gian load tai liệu có thể lâu hơn bình thường )
Nhấn vào nút View full bên dưới để xem toàn màn hình )
Singapore Code of Practice 13; CP13
Bài viết của KS.Nguyễn Hữu Phú
Tp kinh doanh dự án công ty Cp CĐL Đại Việt
Nhà thầu điều hoà không khí VRV chuyên nghiệp hàng đầu Việt Nam
Hãy nhấp vào nút đánh giá nếu thấy bài viết có ích
Tiêu chuẩn thông gió ,cấp gió tươi ,hút khí thải cho điều hòa
Reviewed by Máy làm mát - Máy lọc nước Daikio
on
22:47
Rating: