Tiêu chuẩn thông gió ,cấp gió tươi ,hút khí thải cho điều hòa

Tiêu chuẩn cấp gió tươi và thông gió điều hòa .Singapor standard SS CP13 : 1999 




Code of practive for mechanical ventilation and air -conditionning in buidings.

Table 1 - Outdoor air supply requirement for comfort air-conditioning
Type of buiding/

Occupancy
Minimum outdoor air supply

L/s per floor area
m³/h per m² floor area
Restaurants
2.80
10.00
Dance halls
5.30
19.00
Ofiices
0.65
2.30
Shop, supermarkets and

department stores
1.00
3.60
Lobbies, concourses and corridors
0.25
0.90
Classrooms 
2.60
9.20
Theatres and cinemas
2.00
7.30
Factories and workshops
Light
1.20
4.30
Medium
0.70
2.60
High
0.35
1.30
Hotel guest rooms
15 L/s per room
54 m³/h per room


Table 2- Outdoor air supply for mechanical ventilation in non-conditioned buidings
Type of buiding

Occupancy
minimum outdoor air supply

Air-change/h
Ofiice
6
Restaurant ,canteens
10
Shop, supermarkets and department stores
6
Workshops ,factories
6
Classrooms
8
Theatres and cinemas
8
Lobbies ,concourse , conffidors , staircases and exit
4
Tolets , bathrooms
10
Kitchens (commercial ,institutional and industrial
20
Car Parks
6
Fire commmand center
6
Civil Defence shelters
16
Wasterwater facilities/pumping installation
8


Xêm thêm chi tiết bên dưới (Thời gian load tai liệu có thể lâu hơn bình thường )
Nhấn vào nút View full bên dưới để xem toàn màn hình )

Singapore Code of Practice 13; CP13


Bài viết của  KS.Nguyễn Hữu Phú
Tp  kinh doanh dự án công ty Cp CĐL Đại Việt
Nhà thầu điều hoà không khí VRV chuyên nghiệp hàng đầu Việt Nam

Hãy nhấp vào nút đánh giá nếu thấy bài viết có ích
Tiêu chuẩn thông gió ,cấp gió tươi ,hút khí thải cho điều hòa Reviewed by Máy làm mát - Máy lọc nước Daikio on 22:47 Rating: 5

Biểu mẫu liên hệ

Tên

Email *

Thông báo *

Được tạo bởi Blogger.